Manual
MAX15301 PMBus Command Set User’s Guide 
Rev 1    Page 11 of 53 
VOUT_TRIM 
VOUT_CAL_OFFSET, and the result is sent to the control loop as the output voltage setpoint. 
The value of VOUT_TRIM is not subtracted from READ_VOUT, so nonzero VOUT_TRIM  values  will 
result in a difference between VOUT_COMMAND and READ_VOUT. 
This command is intended to allow an end user of a PMBus device to tailor a specific supply to the 
performance requirements of a specific load device, while retaining use of a “nominal” voltage 
setpoint for all similar load devices. 
VOUT_CAL_OFFSET 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x23 
Format: 
Linear 
Data Bytes: 
2 
Units: 
V 
Transfer: 
Read/Write Word 
Factory Value: 
0x0000 (0V) 
Description/Notes: 
See Section 13.4 of the PMBus Specification Part II. 
In the MAX15301, the value of VOUT_CAL_OFFSET is summed with the value of VOUT_COMMAND 
and VOUT_TRIM, and the result is sent to the control loop as the output voltage setpoint. 
The value of VOUT_CAL_OFFSET is subtracted from READ_VOUT, so VOUT_CAL_OFFSET values never 
result in a difference between VOUT_COMMAND and READ_VOUT. 
This command is intended to allow a PMBus device manufacturer  or an end user  to calibrate  the 
output voltage of  a module (or other power-supply assembly) to match an external reference 
instrument during their final-test process. 
VOUT_MAX 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x24 
Format: 
Unsigned integer mantissa 
Data Bytes: 
2 
Units: 
V 
Transfer: 
Read/Write Word 
Factory Value: 
0x0001 (see Description) 
Description/Notes: 
See Section 13.5 of the PMBus Specification Part II. 
VOUT_MAX mantissa data sent to and from the MAX15301 must be divided by 4096 to determine the 
actual voltage value, according to the fixed value of VOUT_MODE
. 
The factory value of 0x0001 (0.244mV) will be ov
erridden during initialization to 
VOUT_COMMAND x 1.10, unless a specific value has been written to the User Store. 
VOUT_MARGIN_HIGH 
Reference: 
Standard Command 
Lockable: 
Yes 
Command Code: 
0x25 
Format: 
Unsigned integer mantissa 
Data Bytes: 
2 
Units: 
V 
Transfer: 
Read/Write Word 
Factory Value: 
0x0001 (see Description) 