2.2.4  Active, Reactive and Apparent Power Calculation 
Figure 5 shows the signal processing chain for active and reactive power calculations. 
IC1
VC1
WATTSUM_C
Quadrature
Delay
X
LPF
Σ
(TMP)
LPF
Σ
+
X
WATT C
VAR C
Poff
X
VA C
INVERSE
X
PF C
VqC
 N
 N
∑
N-1
n=0
VrmsC
IrmsC
(TMP)
PHASE C
IB1
VB1
WATTSUM_B
Quadrature
Delay
X
LPF
Σ
(TMP)
LPF
Σ
+
X
WATT B
VAR B
Poff
X
VA B
INVERSE
X
PF B
VqB
 N
 N
∑
N-1
n=0
VrmsB
IrmsB
(TMP)
PHASE B
IA1
VA1
WATTSUM_A
Quadrature
Delay
X
LPF
Σ
(TMP)
LPF
Σ
+
X
WATT A
VAR A
Poff
X
VA A
INVERSE
X
PF A
VqA
 N
 N
∑
N-1
n=0
VrmsA
IrmsA
(TMP)
PHASE A
Figure 5. Power and Power Factor Signal Processing Chain 
Active Power 
The instantaneous power is obtained multiplying instantaneous voltage and current samples. The product 
is then averaged over N conversions (accumulation time) to compute active power (WATTA, WATTB and 
WATTC), the aggregate value (WATTS) is the sum of the 3 phases active power average. 
Apparent Power 
The apparent power (VA-A, VA-B, VA-C) is the product of rms voltage (VrmsA, VrmsB, and VrmsC) and 
rms current (IrmsA, IrmsB, IrmsC): 
  VA = I
RMS
 x V
RMS
Reactive Power 
The reactive power is calculated as multiplication of instantaneous samples of current (IA1, IB1, IC1) and 
the instantaneous quadrature voltage (VqA, VqB, VqC). The quadrature voltage is obtained through a 90° 
phase shift (quadrature delay) of the voltage samples. The samples are then averaged over the 
accumulation time interval and updated in the VARA, VARB, and VARC registers. 