Datasheet
78M6610+PSU Data Sheet
3.7.2 AlarmSticky Register (address 0x54)
The AlarmSticky register is an input register that allows configuring individual bits into the Alarms register
to hold the alarm status (“sticky”) until an AlarmReset command is issued. Each alarm can otherwise be
set to auto-reset at the completion of each accumulation interval.
The AlarmSticky register can be saved into flash memory.
Table 3-9: AlarmSticky Register Bits Assignment
Bit Alarm Function
23 N/A N/A
22 OverTemp 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
21 UnderTemp 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
19 ExtOvTemp1 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
18 ExtOvTemp2 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
17-12 Not Used Not used
11 Vsag 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
10 Vsurge 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
9 VdropOut 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
8 OverVolt 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
7 UnderVolt 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
6 OverCurrent 1 = Alarm bit is set until AlarmReset command is issued.
0 = Alarm bit is cleared at every accumulation Interval.
5 OverPower 1 = Alarm bit is set until AlarmReset command.
0 = Alarm cleared at every accumulation Interval.
4 OverFreq 1 = Alarm bit is set until AlarmReset command.
0 = Alarm cleared at every accumulation Interval.
3 UnderFreq 1 = Alarm bit is set until AlarmReset command.
0 = Alarm cleared at every accumulation Interval.
2 N/A N/A
1 N/A N/A
0 Not Used Not used
32 Rev 3