Table 4 lists the narrowband measurement outputs for Outlet 2.
Table 4: Outlet 2 MPU Outputs for Narrowband Method
Output
Location
(hex)
LSB Comment Example
Delta
Temperature
40 0.1 °C
Temperature difference from 22° C.
Note: Duplicate of address 0x00
(see Table 2).
If external temperature is 32 °C
)40?<CR>
Returns:
+10.0
Line
Frequency
41 0.01 Hz
Line Frequency
Note: Duplicate of address 0x01
(see Table 2).
If the line frequency is 60 Hz:
)41?<CR>
Returns:
+60.00
Alarm Status 42
Bit 0 Minimum Temperature
Alarm.
Definition for Status Register
Bit 1 Maximum Temperature
Alarm.
Bit 2 Minimum Frequency Alarm.
Bit 3 Maximum Frequency Alarm.
Bit 4 SAG Voltage Alarm.
Bit 5 MINVA under minimum
voltage on VA input.
Bit 6 MAXVA over maximum
voltage on VA input.
Bit 7 MAXIA_NB maximum
narrowband current exceeded on
Outlet 1.
Bit 8 MAXIA_WB maximum
wideband current exceeded on
Outlet 1.
Bit 9 PFA_NB negative
Narrowband Power Factor
Negative Threshold Alarm for
Outlet 1. Only available is )F2 bit 2
is 1.
Bit 10 PFA_NB positive
Narrowband Power Factor Positive
Threshold Alarm for Outlet 1.
Bit 11 PFA_WB negative
Wideband Power Factor Negative
Threshold Alarm for Outlet 1. Only
available is )F2 bit 2 is 1.
Bit 12 PFA_WB positive
Wideband Power Factor Positive
Threshold Alarm for Outlet 1.
Bit 13 MAXIB_NB maximum
narrowband current exceeded on
Outlet 2.
Bit 14 MAXIB_WB maximum
wideband current exceeded on
Outlet 2.
Bit 15 PFB_NB negative
Narrowband Power Factor
Negative Threshold Alarm for
Outlet 2. Only available is )F2 bit 2
is 1.
Alarms become “1” when
thresholds exceeded.
Note: Additional Status Alert is
Located at addr 0xBD (see Table
8).
Note: When AC voltage input is
less than or equal to 10 V
RMS
,
Only MINVA alarm is active.
All measurements are
forced to 0 except power
factor, which is forced to 1.
Note: The frequency measurement
is forced to 0 as long as the SAG
voltage alarm is active.