Instruction Manual
UG_6612_ 017 6612_OMU_S2+2_URT_V1_14 Firmware Description Document
Rev. 1.0 27
Output
Location
(hex)
LSB Comment Example
Watts A Max 33 mW
Maximum Outlet 1 active power
measured (per second)
Note: Duplicate of address 0x13
(see Table 2).
If the maximum power measured
on Outlet 1 is 200 Watts
)33?<CR>
Returns:
+200.000
Irms_wb A
Min
34 mArms
Outlet 1 minimum wideband rms
current measured.
If the smallest wideband current
measured on Outlet 1 is 1 Amp
)34?<CR>
Returns:
+1.000
Irms_wb A
Max
35 mArms
Outlet 1 maximum wideband rms
current measured.
If the largest wideband current
measured on Outlet 1 is 30 Amps
)35?<CR>
Returns:
+30.000
VARs_wb A
Min
36 mW
Outlet 1 minimum wideband
reactive power measured (per
second).
If the largest VARs measured on
Outlet 1 is 80 VARs
)36?<CR>
Returns:
+80.000
VARs_wb A
Max
37 mW
Outlet 1 maximum wideband
reactive power measured (per
second).
If the largest VARs measured on
Outlet 1 is 300 VARs
)37?<CR>
Returns:
+300.000
VAs_wb A
Min
38 mW
Outlet 1 minimum wideband
apparent power measured (per
second).
If the smallest VAs measured on
Outlet 1 is 80 VARs
)38?<CR>
Returns:
+80.000
VAs_wb A
Max
39 mW
Outlet 1 maximum wideband
apparent power measured (per
second).
If the largest VAs measured on
Outlet 1 is 300 VARs
)39?<CR>
Returns:
+300.000
Power
Factor_wb A
Min
3A –
Outlet 1 minimum wideband power
factor measured. Minimum is
defined as the most negative or
least positive number.
If minimum wideband power factor
measured on Outlet 1 is –0.6
)3A?<CR> Returns:
-0.600
Power
Factor_wb A
Max
3B –
Outlet 1 maximum wideband power
factor measured. Maximum is
defined as the most positive or
least negative number.
If maximum wideband power factor
measured on Outlet 1 is 0.9
)3B?<CR> Returns:
+0.900
Phase
Angle_wb A
Min
3C
–
Outlet 1 minimum wideband phase
angle measured.
If the minimum wideband phase
angle measured on Outlet 1 is 10
degrees
)3C?<CR>
Returns:
+10.000
Phase
Angle_wb A
Max
3D –
Outlet 1 maximum wideband phase
angle measured.
If the maximum wideband phase
angle measured on Outlet 1 is 70
degrees
)3D?<CR>
Returns:
+70.000
Reserved 3E-3F – Reserved
Reserved