Maxiflex T2 CPU User Manual 48 -© Omniflex
UMM124XBR04.pdf
DIT Number Description
64100 Serial Port Setup
This register sets up the communications parameters for the serial port on the CPU.The
format of this register is as follows:
015 1234567891011121314
Stop bits
Parity
Data bits
Baud Rate
Not Used
Half/Full Duplex
RTS/CTS Handshaking
Transmission Mode
Protocol
Stop Bits: 1 = 1 stop bit, 0 = 2 stop bits
Parity: 00 = none, 01 = odd, 10 = even
Data Bits: 1 = 8 data bits, 0 = 7 data bits
Baud: 0000 = 300 baud
0001 = 600 baud
0010 = 1200 baud
0011 = 2400 baud
0100 = 4800 baud
0101 = 9600 baud
0110 = 19200 baud
0111 = 38400 baud
RTSCTS Handshaking: 1 = ON, 0 = OFF
Transmission Mode: 1 = ASCII, 0 = RTU(Binary)
Protocol: 00 = Reserved
01 = Modbus
10 = User Protocol
64101 64150 Network Routing Table
These registers contain the data that allows the T2 CPU to route packets across
networks e.g. routing a packet from a Modbus network connected to the serial port, to a
Conet network connected to the Conet port. An MS Excel Spreadsheet is used to
generate the data for this table. This spreadsheet is available from Omniflex if the user
requires to route messages with the T2 CPU.
64101 Setup for Network 1
The default setting for this register is 64768 when no User routing table has been
configured. If a routing table has been configured and the User wishes to revert back to
the default setting, he may simply write zero to this register and the default settings will
be invoked
64102 Setup for Network 2
64103 Setup for Network 3
64104 Setup for Network 4
64105 Setup for Network 5