User`s manual
Maxiflex T2 CPU User Manual 43 -© Omniflex
UMM124XBR04.pdf
DIT Number Description
604-605 Raw Digital Output Data for I/O Slot 8
606-607 Raw Digital Output Data for I/O Slot 9
608-609 Raw Digital Output Data for I/O Slot 10
610-611 Raw Digital Output Data for I/O Slot 11
612-613 Raw Digital Output Data for I/O Slot 12
614-615 Raw Digital Output Data for I/O Slot 13
616-617 Raw Digital Output Data for I/O Slot 14
618-619 Raw Digital Output Data for I/O Slot 15
620 – 649
Raw Digital Input Data Area
The Raw Digital Input values scanned by Maxiflex Digital Input modules can be
read from this data area. The data is in packed bit form such that a single DIT
register comprises 16 channels of an input module.
32 channels (or 2 DIT registers) are allocated per I/O Slot starting from DIT 620.
The Bit representation for each channel is provided below.
NOTE: The Raw data for a given I/O Slot will clear to zero if there is no input
module installed in that I/O Slot.
620 – 621 Raw Digital Input Data for I/O Slot 1
620
Raw Digital Input Data for I/O Slot 1, Channels 1 - 16
Input channels 1 to 16 are packed into this DIT register as shown:
015 1234567891011121314
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Channel 9
Channel 10
Channel 11
Channel 12
Channel 13
Channel 14
Channel 15
Channel 16
If Bit n is 1, then Input channel n is ON
If Bit n is 0, then Input channel n is OFF
621
Raw Digital Input Data for I/O Slot 1, Channels 17 – 32
Input channels 17 to 32 are packed into this DIT register as shown: