User`s manual
Maxiflex T2 CPU User Manual 39 -© Omniflex
UMM124XBR04.pdf
DIT Number Description
Global ID of the CPU on the Serial Port. Only applies if the Network Routing Table
is configured to include this port. Note that as the default Network Routing Table
does not include this port, the default Global ID setting is set to 255 which is an
invalid Global ID.
76
Network Port Local ID
This is the local ID setting on the Network Port Dipswitch, switches 1 to 7.
77
Network Port Global ID
Global ID of the CPU on the Network Port. The default Network Routing Table
includes this port at a Network offset of 127. This the Global ID for the CPU equals
the network offset of 127 + Local ID in the default case.
78
Serial Port dipswitch setting
79
Network Port dipswitch setting
80 - 87
System Timers
CPU count down timers decremented by the Operating System until zero is
reached. Values entered are decremented by 1 every 10 milliseconds.
For example, enter 100 to time for 1 second. The largest timer available is 655350
ms or about 11 minutes.
80 System Timer 0
81 System Timer 1
82 System Timer 2
83 System Timer 3
84 System Timer 4
85 System Timer 5
86 System Timer 6
87 System Timer 7
88 – 109 RESERVED
110 – 349
Raw Analogue Output Data Area
Raw Analogue Output values written to this data area are copied to corresponding
Maxiflex Analogue Output modules automatically by the CPU. Individual analogue
output channels are referenced by I/O Slot and Channel number for easy access.
16 Channels are allocated per I/O Slot. The following formula may be used to
access output channels:
Output DIT = 110 + (channel-1) + (I/O_Slot –1) * 16
Refer to Appendix 3 for the data format required to drive Analogue Output
Modules.
110 - 125 Raw Analogue Output Data for I/O Slot 1, Channels 1-16
110 Raw Analogue Output for I/O Slot 1, Channel 1
111 Raw Analogue Output for I/O Slot 1, Channel 2
112 Raw Analogue Output for I/O Slot 1, Channel 3
113 Raw Analogue Output for I/O Slot 1, Channel 4