Hysteresis:
0 to 99%
Signal source:s
Analog input signal
Integrated value
Digital input
Number:
4 in basic unit (can be extended to 8 relays, option)
Electrical specifications:
Relay type: changeover
Relay switching capacity: 250 V AC / 30 V DC, 3 A
Switch cycles: typically 10
5
Switching frequency: max. 5 Hz
Minimum switching load: 10 mA / 5 V DC
Galvanic isolation towards all other circuits
!
Note! Assignment:
Mixed assignment of low and extra-low voltage circuits is not permitted for neighboring relays.
10.2.6 Transmitter power supply
Transmitter power supply 1, terminal 81/82 (optionally intrinsically safe):
Electrical specifications:
Output voltage: 24 V ± 15%
Output current: max. 22 mA (at U
out
16 V, sustained short-circuit proof)
Impedance: 345 Ω
Approvals:
•ATEX
•FM
•CSA
Transmitter power supply 2, terminal 91/92:
Electrical specifications:
Output voltage: 24 V ± 15%
Output current: max. 250 mA (sustained short-circuit proof)
10.3 Installation
10.3.1 Installation instructions
Mounting location
Panel, cutout 92 x 92 mm (3.62x3.62 inch) (see 'Mechanical construction').
Orientation
Horizontal +/- 45° in every direction