Note!
The errors specified above can be evaluated with a relay in the operating mode "Alarm" and
"Alarm inverse".
9.2.2 Incorrect entries
E 105 Bus error reading the relay
data after power-up
Incorrect relay data Reset relay data
E 106 Universal card bus error Faulty universal input
functioning
Replace universal card, notify
Service
E 210 Pulse output, pulse buffer
overflow
A maximum of 10 pulses are
buffered
Set the parameters of the
pulse output in such a way
that the maximum frequency
is not exceeded
E 221 Pump error, digital input 1
Relay goes to failsafe mode
Acknowledge error via
operation or switching power
on/off
E 222 Pump error, digital input 2
E 223 Pump error, digital input 3
E 224 Pump error, digital input 4
E 290 Number overshoot due to
decimal point shift
Decimal point position
cannot be altered
Check decimal point position
and number range
Error code Cause Effect Remedy
Error code Description Reaction at device
E 290 The number of digits after the decimal point
cannot be increased due to number overflow of
the dependent parameters.
Error code is shown on the display until a key is
pressed.