Operating instructions

Commissioning
56
6.3.10 Support points of linearization table - LINPOINTS 1..X/M23..MXX
Displays the set value pairs of the linearization table. This menu item is only visible if a
linearization table was configured under Section 6.3.9 and "Yes" was selected in the "Show
points" parameter in the "LIN. TABLE/M21" menu.
6.3.11 Operating parameter - PARAMETER/M55
In this menu item, configuration options such as the user code, failsafe mode of RIA452 to
NAMUR etc. can be configured.
Function
(menu
item)
Parameter setting Description
Point
Used
Discard
Use or discard support point.
X value
-99999..99999 X-value of the linearization table. Corresponds to the
input value.
Y value
-99999..99999 Y-value that belongs to the previous X-value.
Corresponds to the converted measured value.
Function
(menu
item)
Parameter setting Description
User code
9999 The option of editing the operating parameters is locked
after entering a 4-digit digital sequence (limit value
code).
This lock is indicated on the display with the "key"
symbol.
Limit Code
Off
On
If the limit value code function is activated, only the
configuration of the limit values is permitted. All other
operating parameters cannot be modified.
Activation of restricted operation is indicated on the
display with the "key" symbol.
The item is only displayed if a user code was assigned.
Prog. name
ILU10xA Displays the name of the device software currently
installed.