Operating instructions

Commissioning
55
Level 10 m
Numeric display should show 1500 (m
3
)
Bar graph should show 100%
20 mA should be present at the analog output
The following parameters must be configured for the example above:
!
Note!
ReadWin
®
2000 operating software supports the generation of a tank linearization table.
Here you can find a tank linearization generator which you can use to generate the linearization
table for standard and customer-specific tanks.
Point
1 2 3 4 5 6 7 8 9 10
Sensor
signal
(mA)
X
value
4,0
X
value
4.32
X
value
4.64
X
value
4.96
X
value
5.28
X
value
5.6
X
value
5.92
X
value
6.24
X
value
6.56
X
value
20.0
Display
value
(m
3
)
Y
value
0
Y
value
20
Y
value
50
Y
value
85
Y
value
115
Y
value
160
Y
value
210
Y
value
280
Y
value
400
Y
value
1500
Menu Function (menu item) Setting value
LIN. TABLE / M 21 Counts
Dimension
Show points
Number of support points (10)
Dimension of lin. value (m
3
)
Display support points (Yes)
LINPOINTS 1 to 10 / M23 to 32 Each point
Each X value
Each Y value
Use point (Used)
X-value (as in table above)
Y-value (as in table above)
ANALOG OUT / M 3 Ref. num
Out range
Fail mode
Fail value
Output value (lin tab)
Signal type (0-20 mA)
Failsafe mode (const)
Value in event of error (21 mA)
DISPLAY / M 2 Ref. num.
Ref. bargraf
Reading on display (lin. table)
Signal source for bar graph (lin tab)