Operating instructions

Commissioning
31
Fail mode
Hold
const
Min
Max
Output value if a sensor or device error occurs.
Hold = last valid value
Const = freely selectable value
Min = output value 3.5 mA for 4 to 20 mA,
otherwise 0 V or 0 mA
Max = output value 22.0 mA for 0/4 to 20 mA,
otherwise 1.1 V or 11 V
Fail value
0..999.99
0.00
The freely selectable value for "Fail mode = Const" can
be set here.
Current output: 0 to 22 mA
Voltage output: 0 to 11 V
Simu mA
OFF
0.0 mA
3.6 mA
4 mA
10 mA
12 mA
20 mA
21 mA
Simulates the current output and outputs the selected
current at the output, regardless of the input value.
Is automatically set to OFF when the Simu mA menu
item is exited.
Simu V
OFF
0.0 V
5.0 V
10.0 V
Simulates the voltage output and outputs the selected
voltage at the output, regardless of the input value.
Is automatically set to OFF when the Simu V menu
item is exited.
Function
(menu
item)
Parameter setting Description