Specifications
30
MX Protection, Control and Monitoring Features FCD LMENTB2300-01 – 07/08
Figure 12.2 – Optional Features Wiring Diagrams
ALARM FEEDBACK
THE ALARM CONTACTS (R) MAY BE CONFIGURED FOR ANY
FUNCTION SHOWN IN FIGURE 12.1, AND MAY BE INDIVIDUALLY
CONFIGURED AS NORMALLY OPEN, NORMALLY CLOSED OR
BLINKER LATCHED CONTACTS.
CONTACT RATINGS:
R1, 2, 3, 4, 5, 6, 7, 8 – 5.0 AMPS AT 250 VAC, 30 VDC
EXTERNAL LOAD – APT & ATT
4-20 mA SIGNAL - 470 ohms MAXIMUM for 99.9% accuracy/750 ohms
MAXIMUM for 99% accuracy
0-10 VDC SIGNAL - 2700 ohms MINIMUM for 99% accuracy and 1000
ohms for 99.9% accuracy.
MODUTRONIC
COMMAND SIGNAL = 4-20 mA
INPUT IMPEDANCE = 150 ohms
INPUT CAPACITANCE = 0.1 µF ±30%
NOTE:
ACTUATORS SUPPLIED WITH “R” DEVICES ARE SHIPPED WITH
DEFAULT SETTINGS AS SHOWN ON THE DIAGRAM, UNLESS
OTHERWISE SPECIFIED.
EXACT END POSITION INDICATION
ON TORQUE-SEATED VALVES, THE LCD AND “S” CONTACTS
CONFIGURED AS END-OF-TRAVEL LIMITS AUTOMATICALLY PROVIDE
EXACT END POSITION INDICATION.
ANALOG INPUT
STANDARD SIGNAL 4-20 mA
INPUT IMPEDANCE = 350 ohms
INPUT CAPACITANCE = 0.1 MF 30%
99% ACCURACY
CONFIGURABLE SCALING
42
43
R8
DEFAULT SETTING
ALARM RELAYS – R2
MOTOR
OVERTEMP
REMOTE
SELECTED
OVERTORQUE
ANALOG
I/P
R7
R6
R5
37
36
39
38
41
40
MODUTRONIC
STANDARD SIGNAL 4-20mA
19
20
-ve ANALOG INPUT
+ve ANALOG INPUT
18
17
APT
or
A T T
4-20mA OUTPUT
0-10VDC OUTPUT
COMMON -Ve
15
ANALOG POSITION OR TORQUE
TRANSMITTER
16
1
A T T
4-20mA OUTPUT
0-10VDC OUTPUT
COMMON -Ve
2
ANALOG TORQUE
TRANSMITTER
50
51
R4
DEFAULT SETTING – SAME AS “S”
ALARM RELAYS – R1
VALVE
CLOSED
VALVE
OPEN
VALVE
CLOSED
VALVE
OPEN
R3
R2
R1
45
44
47
46
49
48
Optional voltages or currents; 0-20 mA, 4-20
mA, 0-10 VDC, 2-10 VDC, 0-5 VDC, 1-5 VDC
4-20 mA OR 0-50 Vdc INPUT
12