Specifications
22
MX Protection, Control and Monitoring Features FCD LMENTB2300-01 – 07/08
Figure 9.2 – Configuring the MX Actuator
1 Place selector switch in “STOP.” The LCD
display will read “% OPEN” and “STATUS OK.”
Operate the selector switch to the (YES) (NO)
(YES) positions. The message “SETUP?” will
be displayed for 10 seconds. Answer “YES” to
enter setup routine.
2 All parameters may be configured by
answering “YES”/ “NO” questions. For
example, entering a “NO” response to the
displayed screen will change the displayed
torque value. Select “YES” when the desired
value is displayed.
Configuration screens are displayed in English. Languages such as Spanish, French, German, Italian,
Portuguese, Mandarin, Russian, Bahasa Indonesia, and Katakana are also available and can be
configured via the actuator control panel.
A three-digit numeric password is included as part of the initial setup procedure to prevent unauthor-
ized changing of the configured parameters. If the password is entered incorrectly, settings may be
viewed, but not changed. The default value for the password is 100.
10. MX Specifications
The MX is the most rigorously tested non-intrusive actuator in the industry and complies with all
pertinent global requirements. Please contact the factory should your requirements exceed the listed
parameters.
Global certifications
Standard Non-hazardous certifications - The normal operating temperature range for weatherproof
applications is from -30°C to +70°C (-22°F to +158°F). Options are available to -60°C (-76°F).
FM – NEMA 3, 4, 4X and 6.•
CSA – Type 3, 4, and 6.•
IEC – IP 68 to 15 m for 96 hours.•
Submersion – NEMA 6 (6 ft–30 min), IEC529, IP68 (15 m–96 h), Limitorque specification •
(20 ft–24 h)
Saliferous (Salt) spray – 1500-hour test per ASTM B117-1985.•
Standard Explosionproof certifications - The normal operating temperature range for explosionproof
applications is from -30°C to +65°C (-22°F to +149°F). Options are available to -50°C (-57°F) for FM
and CSA.