Specifications

13
flowserve.com
MX Protection, Control and Monitoring Features FCD LMENTB2300-01 – 07/08
as point-to-point, bus with spurs, daisy chain, tree, or a combination of these. The PB device has
network features that include:
High-speed communications up to 31.25 kbits/s with Manchester coding•
Master-to-slave communication•
Bus powered for 9-32 VDC and 15 mA per actuator•
Stand-by communication channel•
One analog in and one analog out, four digital input and up to eight digital output function blocks•
Device descriptions configurable by user•
3.6 Device Type Manager (DTM) for Profibus DP & PA
A software component which can be downloaded from www.limitorque.com and integrated into Field
Device Tool (FDT) frames for:
offline/online parameterization•
configuration•
status updates•
diagnostic retrieval•
3.7 DeviceNet
DeviceNet complies with CAN based protocol and provides the following features:
DeviceNet Group 2 Server implementation.•
Bus Powered Network Interface allows power alarm information to be communicated when •
actuator loses main power. The actuator does NOT drop off the network when 3-phase power is
lost.
Standard Polled I/O Connection•
Standard Bit Strobed I/O Connection•
Standard Change of State / Cyclic I/O Connection•
Standard explicit connections defined as:•
Various Assembly Objects and sizes that allow the network user to determine how much data •
to transfer to accommodate network installation data throughput requirements.
Automatic BAUD rate detection.•
Node Address configurable via local setup menu, or via the remote network user.•
Broadcast or group network originated ESD support.•
The following commands and information may be transmitted over the DeviceNet network:
“OPEN,” “STOP,” and “CLOSE” commands•
“ESD” and “MOVE–TO” position commands•
Actuator status and alarm messages•
Six digital inputs and one analog input and output for user•
A surge-protected and isolated communication channels•
MX control panel configuration•
Torque output (for reference only) and position feedback•
Four digital outputs (standard) with four additional digital outputs (optional)•
Please see Section 13 for network connection topologies and cabling recommendations.