Technical data

MD720-3 in OPC Mode
SINAUT MICRO SC
C79000-G8900-C210
65
9. In the Start-menu select Connect to and choose the connection you just have
set up, e.g. Service-MD720.
10. Click two times OK to finish the Modem Configuration and the Properties
windows
To establish a service connection
As soon as the network connection is set up you can establish the service
connection.
1. Click Start.
2. In the Start-menu select Connect to and choose the connection to the SINAUT
MD720-3.
3. Type in the user name (Default: service) and the password (Default: service)
and the click Dial.
4. When the connection is established in the Windows task bar a connection icon
is displayed.
5. Click Start, All Programs, Accessories, Command Prompt.
6. Enter: C:\WINDOWS>ftp 192.168.0.8
Then press Enter.
7. You are asked for the user name (Default: service) and for the password
(Default: service). Enter both in the right case sensitive spelling.
8. As soon as the connection is established successfully you get the message
„230 User logged in“. The prompt changes to „Ftp>“.
To update the firmware of the SINAUT MD720-3
As soon as the service connection is established you can start to upload the
firmware.
1. With Notepad (belongs to Windows) create a file with the name !cmdfile. The
file name must not have any extension (e.g.: .txt). The first line in this file is:
STORE FirmwareName.BIN
Instead of „FirmewareName.BIN“ write the name of the new firmware file.
2. At the Ftp>-prompt enter: put FirmwareName.BIN
Press Enter. Instead of „FirmewareName.BIN“ write the name of the new
firmware file.