Technical data

PLC Library SINAUT MICRO SC
SINAUT MICRO SC
40 C79000-G8900-C210
AP_PASSWORD
(DWORD (Saving address of string))
Password for registration at GPRS access point.
DNS
(DWORD (Saving address of string))
IP addresses of DomainNameServer of GSM provider.
If two DNS servers are to be specified, these can be divided by semicolon (;)
(DNS1;DNS2), e.g. „194.25.2.131;193.254.160.1“.
CLIP
(DWORD (Saving address of string))
List of all valid dial-in numbers at the station. Several listing entries are divided by
semicolon (;). The sequence is specified, in each case three numbers for the dial-in
to the application (COM) and for the dial-in to the modem service-operation
(SERVICE).
<COM_CLIP_0>;<COM_CLIP_1>;<COM_CLIP_2>;<SERVICE_CLIP_0>;<SERVI
CE_CLIP_1>;<SERVICE_CLIP_2>
Only calls are accepted of valid phone numbers.
The entered numbers for SERVICE_CLIP and COM_CLIP must be different. If
same numbers has been entered the SERVICE_CLIP priority.
Wildcard characters (*) can be used for the definition of phone number groups.
Example:
+49123123* all numbers are accepted starting with +49123123.
Caution
Enter as CLIP a phone number, which you can use to call the PLC or the SINAUT
MD720-3, to download a new software.
If you do not enter a CLIP, you cannot use this teleservice function.
BUSY
(BOOL)
0 Inactive
1 The initialization sequence is in process at the moment.