Technical data

Troubleshooting
SINAUT MD720-3
C79000-G8900-C210
57
that the internet address of your server (IP address or hostname) is correctly
entered in your PLC program module (IP_ADDRESS_CS Parameter),
that the DynDNS server is frequently updated, if you are using a DynDNS
Service to get a fixed address for your SINAUT MICRO SC.
SINAUT MICRO SC and SPS do not connect
The Status indication
of the SINAUT MICRO SC shows, that the connection
between SINAUT MICRO SC and SINAUT MD720-3 is established, but that the
PLC is not reachable.
Please check, if the value for Station number corresponds to the values being
entered into the PLC program module.
Please check, if the PPI cable is configured as shown in the System manual.
Data loss between SINAUT MICRO SC and PLC
A loss of data between SINAUT MICRO SC and PLC may occur, because the used
PPI cable is only capable of half-duplex connections.
Please make sure that you wait at least 5 to 10 seconds between two requests
from SINAUT MICRO SC to the PLC.
The LED “S” blinks fast (4 times per second)
If the SIM card is inserted correctly and the SIM card is not PUK-blocked, the LED
“S” blinks fast and indicates a SIM Problem. Please check and eventually reset the
SIMSTATE, refer to System manual SINAUT MD720-3, chapter PIN in OPC-Mode.