Technical data
PLC Library SINAUT MICRO SC
SINAUT MD720-3
42 C79000-G8900-C210
Caution
Enter as CLIP a phone number, which you can use to call the PLC or the SINAUT
MD720-3, to download a new software.
If you do not enter a CLIP, you cannot use this teleservice function.
BUSY
(BOOL)
0 Inactive
1 The initialization sequence is in process at the moment.
DONE
(BOOL)
1 The initialization has been successfully accomplished.
ABORTED
(BOOL)
1 The initialization has been aborted due to an error.
ERROR
(WORD)
Error number, describing the result of the processing.
A list of all error numbers and their meaning is to be found in chapter 0