Technical data
SINAUT MICRO SC configuration
SINAUT MD720-3
32 C79000-G8900-C210
GPRS modem password
The password used by the GPRS modem for login at the server. This password
must match MODEM_PASSWORD when calling WDC_INIT in the PLC program.
This password is proposed depending on the station number but can be changed
at any time.
SPS status monitoring
Indicates if and how the connection to the PLC is monitored in periodic intervals.
• Status monitoring deactivated
The connection to the PLC is not monitored. No additional costs are created.
• Status monitoring by value updates
The connection to the PLC is monitored by updating all values from the PLC in
the configured time interval. With this option it might not be necessary to update
analogue values and counters by the PLC program in periodic intervals.
• Status monitoring by RealTimeClock synchronization
The connection to the PLC is monitored by synchronizing the PLC real time
clock in the configured interval.
Even if this option is not selected, the PLC real time clock is synchronized once
a day.
The Interval determines the frequency for status monitoring.
Notice
The status monitoring has the function to test and to indicate, if the configured
connection is still available. Often the status monitoring function is also necessary
to keep the connection alive. A lot of network operators disconnect connections
automatically if no data has been transmitted for a period of time. This can be
avoided, when frequently status requests are transmitted.
If you do not have already experiences with your GPRS service, you should
select an interval of 15 minutes and you should use Status monitoring by
RealTimeClock synchronization.
Try if the connections are stable also, if you use intervals greater than 15 minutes
and accordingly select smaller intervals if your connections are often interrupted.
Warning
With frequent status test calls higher costs may be caused, because of higher
data volume.
Comment
Any comment regarding this station.