Technical data
Configuration software for SINAUT ST7
1.9 Subscriber administration in the SINAUT configuration tool
Software
96 System Manual, 07/2009, C79000-G8976-C222-07
Properties - Local Connection
dialog for the TIM
This dialog displays the properties of the local LAN connection of a TIM module to its CPU.
Figure 1-49
Properties - Local Connection
dialog (TIM)
For the local connection of the TIM module, you can set the following here:
●
Send Keepalives for this connection:
If this option is enabled, keepalive messages are sent on this connection at the intervals
set in the network configuration for the TIM.
●
Queue entries [number]
:
Range of values: 10 .. 256
Default: 64
The number of queue entries is the number of messages that the TIM module can buffer
prior to transmission. In general, you do not need to change the default setting. It may be
useful to increase the value for a master TIM to relieve message traffic if there is a heavy
load at certain times due to the transfer of large amounts of data, for example archive
data.
Properties - Local Connection
dialog for the CPU
This dialog visualizes the properties of a local LAN connection of a CPU and allows the
following properties to the selected:
● CPU modules with X connections / P bus connections:
– The
length of the send buffer [bytes]
for these connections
Range of values: 76 ... 65382 bytes