Technical data

Configuration software for SINAUT ST7
1.6 Configuring networks and network nodes in STEP 7 / NetPro
Software
System Manual, 07/2009, C79000-G8976-C222-07
59
Note
If there is an asterisk after one or two addresses, the WAN address is not unique and must
be changed.
Time Slots
- Only in networks with a suitable polling mechanism
In the
Time Slots
tab, you can specify which time slots are used for transmission in the
Polling with time slots
and
Multi-master polling with time slots
modes.
To allow communication, at least one time slot must be selected since the master can only
poll within the selected time range.
Figure 1-27
Properties - SINAUT Dedicated Line
dialog,
Time Slots
tab
When setting the parameters for time slots, follow the steps below:
1. Specify the
No. of time slots
per minute. The
Length of one time slot
is calculated from
this.
2. In the
Master stations
list, in the
Stat. Addr.
column, select the station address of the
master station of the subnet.
3. In the
Time slots
list, in the
sec to sec
column, select the required time slot for calling this
master station.
4. Click the
assign station # to slots
to assign the selected time slot to the selected master
station.