Technical data
Configuration software for SINAUT ST7   
1.6 Configuring networks and network nodes in STEP 7 / NetPro 
  Software 
56  System Manual, 07/2009, C79000-G8976-C222-07 
Range of values: 40 .. 240 
Default: 240 
Note 
The default of 240 for the maximum message length should, whenever possible, not be 
changed since PG routing will not work with a maximum message length less than 240. 
● 
Connection type
: 
Range of values: Half duplex, duplex 
Default: Duplex 
● 
Baud rate
: 
This is the speed at which the TIM and modem communicate. The transmission rate in 
the current network is decided by the modem and is normally identical to that of the 
modem. 
If you want to operate the modem at a speed that is not one of the default speeds, set the 
next higher speed here (for example 19200 bauds with the modem operating and 14400 
bauds). 
–  Range of values on dedicated lines and in the spontaneous network: 
50, 100, 150, 200, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 bauds 
–  Range of values in the dial-up network: 
1200, 2400, 4800, 9600, 19200, 38400 bauds 
–  Default: 1200 bauds 
● 
Cancel parameter
 (with dial-up networks only): 
This is the number of attempted dialing attempts until the attempt is finally aborted. 
Range of values: 0 ... 127 
Default: 0 
–  Cancel parameter = 0: 
The call attempts are finally aborted when a connection was established 127 times in 
a row but no data could be transferred. 
–  Cancel parameter = 1 ... 127: 
The call attempts are finally aborted when a connection was unsuccessful n times in a 
row, regardless of whether a connection could be established at all or whether data 
could not be transferred on an established connection. 
● 
Redialing attempts
 (with dial-up networks only): 
This is the number of attempted calls until until a disruption is reported. 
Range of values: 1 ... 127 
Default: 3 
● 
Customer identification
 (with dial-up networks only): 
The customer identification is used to specify whether connections can only be 
established to partners permitted for the network. The customer identification has the 
function of password protection in the relevant network. 
Range of values: 0 ... 65535 
Default: 0 
For more information on SINAUT ST1, refer to release 05/2007 of the manual. 