Technical data
SINAUT Diagnostics and Service tool
3.7 Messages in the diagnostic buffer of the CPU
Software
System Manual, 07/2009, C79000-G8976-C222-07
423
Diagnostic messages and activation of the group error LED
If an error occurs during startup, the read group LED (SF) of the TIM lights up and a
message to this effect is entered in the diagnostic buffer of the TIM.
If the TIM is installed as a CP in an S7-300 rack, a diagnostic interrupt is sent to the CPU.
The following table contains a summary of all error messages that caused the group error
LED (SF) to light up.
Table 3- 20 Classification of the group error messages of the TIM
Error class Detailed event in the diagnostic message
Internal error 0061h
0063h - 0067h
0069h
0078h - 0080h
0083h
06B0h
External error 0320h
No parameter assignment: 0070h
0071h
0620h
Bad parameter assignment 0077h
0081h
0110h
0112h
0300h
031C
0500h
0620h
RAM error 0085h
0086h
3.7 Messages in the diagnostic buffer of the CPU
Introduction
The SINAUT TD7onCPU software package generates a series of operating and error
messages that are entered in the diagnostic buffer of the CPU. These can be displayed in
SINAUT / TD7 CPU Diagnostics
. If a PG is connected and if this is registered for CP
messages, these diagnostic messages are displayed on the PG immediately when they
arise.