Technical data

SINAUT Diagnostics and Service tool
3.5 Message protocol diagnostics
Software
System Manual, 07/2009, C79000-G8976-C222-07
397
1. Make sure that MPI address 3 is either free or is occupied by the module on which you
want to install.
2. Select the TIM you want to repair in the
SINAUT subscriber list
of the open project.
3. Start the function by selecting the
SINAUT / Repair
menu and then
Complete
reinstallation
in the context menu. The
Firmware Install
dialog opens. The version
installed on the PG is displayed. If the firmware on the PG is incomplete, a message to
this effect is also displayed.
4. Click on the
Update details
button if you require a detailed information on the firmware
update. The
Installation details
dialog opens.
5. Click on the
Start Installation
button in the
Firmware Install
dialog to start the repair. The
following dialog
Download
informs you of the current progress of the procedure.
6. On completion of the repair, a dialog opens with a message to this effect. Confirm the
message with
OK
.
Installation details
dialog
The
Installation details
dialog that can be opened from the
Firmware Install
dialog displays
detailed information on the repair. For each firmware component, the function and version on
the TIM module and on the PG are shown and you can also see whether the component will
be copied, replaced, ignored or deleted during the repair.
The various actions have the following significance:
copy: The file is copied from the PG to the TIM module.
replace: The file on the TIM module is replaced by the file on the PG.
ignore: The file is not affected by the repair.
delete: There is no newer version for the file. The existing file is no longer required and is
deleted during the repair.
3.5 Message protocol diagnostics
Introduction
To read out messages, SINAUT ST7 provides you with the option of recording messages
transferred in the CPU, TIM and ST7cc/ST7sc PC components; in other words, to archive
them in protocols.
The following protocol types are distinguished:
Testcopy DB:
This is used to record messages on a CPU module.
ST7cc/ST7sc protocol:
This is used to record messages in SINAUT ST7cc or SINAUT ST7sc.
TIM message protocol:
This is used to record messages received and sent by a TIM module.