Technical data
SINAUT Diagnostics and Service tool
3.3 SINAUT diagnostics
Software
388 System Manual, 07/2009, C79000-G8976-C222-07
Parameter block Parameter
- Operating mode: Interrupt (Block)
- # of subscribers: 2
Subscriber data SDB
The subscriber data SDB contains information on the settings for data of all subscribers of a
project. The content of a subscriber SDB is shown below based on an example.
Table 3- 10 Example of the information of a subscriber data SDB (type 3203)
Subscriber Parameter
# of subscribers: 5
Subscriber 1 Subscriberno.: 1
Subscriber info: 0x0
ST7-CPU
additional info: 0x0
send NO status object to subscriber
count of connection blocks: 2
device | subnet ID | CFB/MPI | state | connection | STA
int. WAN | 008a00000001 | 0 | remote | WAN connection.,ST7 |
0x01
ext. WAN | 008a00000001 | 0 | remote | WAN connection.,ST7 |
0x01
count of partner blocks: 1
subscriber no.: 2
Subscriber 2 Subscriberno.: 1003
Subscriber info: 0x1
ST7 TIM
etc.
Connection data SDB
The connection data SDB contains information on the parameter settings of the local X
connections of a TIM module to their CPU. This is illustrated below based on an example.
Table 3- 11 Example of the information of a connection data SDB (type 3205)
count of X com. blocks: 1
block
1
connection type
static
loc. device ID
0
target MPI
2
LAN connection SDB
The LAN connection SDB contains summarized information on the parameter assignment of
all LAN connections on a TIM module. This is illustrated below based on an example.
Table 3- 12 Example of the information of a LAN connection SDB (type 3201)
local subscriberno.:
local MPI address:
1002
3
count of LAN blocks: 2