Technical data
Configuration software for SINAUT ST7
1.5 Setting TIM module parameters
Software
System Manual, 07/2009, C79000-G8976-C222-07
33
Both TIMs synchronize the stations connected over a dedicated line or dial-up network by
synchronizing the TIMs in the stations that, in turn, supply their own CPU. In these
networks, you do not need to make settings for the TIMs. These TIMs obtain their
parameters from the time parameter settings made centrally for the particular SINAUT
network (dedicated line or dial-up network) refer to the section: Setting parameters for
SINAUT networks, Time Services tab).
● Station1, TIM 32
Time synchronization on the S7-300 backplane bus must be enabled for this TIM; in other
words, the TIM then supplies the S7-300 CPU with the current time over the backplane
bus. An interval of 1 minute is recommended.
Note
If a TIM synchronizes an S7-300 CPU over the backplane bus, no synchronization
settings are necessary for the S7-300 CPU in HW Config. The SINAUT software on the
CPU (TD7onCPU, FC TimeTask) handles the synchronization by using the
synchronization message of the TIM to set the CPU clock.
● Station 2, TIM 3V-IE
Here, there are two situations to be taken into account:
– A SINAUT program (TD7onCPU) is running on the CPU:
You set the time synchronization on the S7-300 backplane for the TIM.
– The SINAUT program is configured on the TIM 3V-IE (TD7onTIM):
You do not need to enable time synchronization on the TIM.
Although there is no SINAUT program on the CPU, the CPU can nevertheless by
supplied with the time of day when necessary. In this case, the TIM supplies the time
data to its inputs. This is explained in detail elsewhere (refer to the
section: Synchronization of the CPU time with TD7onTIM).
● TIM Station 3
This TIM handles the SINAUT communication for the S7-400 "Station 3". Here, you will
need to enable time synchronization on the relevant Ethernet interface of the TIM as
master. An interval of 1 minute is recommended.
● Station 3
No settings need to be made for the S7-400 CPU nor for the CP 443 in HW Config. The
SINAUT software on the CPU (TD7onCPU, FC TimeTask) handles the synchronization
by using the synchronization message of the TIM to set the CPU clock.
The next figure shows a further excerpt from the sample project which will be used to explain
further details on synchronization, particularly in an Ethernet network.