Technical data

Software
System Manual, 07/2009, C79000-G8976-C222-07
329
SINAUT Diagnostics and Service tool
3
3.1 Overview of the functions and operation of the SINAUT Diagnostics
and Service tool
Introduction
The SINAUT Diagnostics and Service tool provides the user with functions for checking
connections, interfaces and communication as well as the firmware and software
components of the network subscribers of a SINAUT installation.
The most important functions are as follows:
Reading the diagnostic data from a TIM or CPU module
Reading the diagnostic buffer
Checking and setting the module time
Reading the module parameter assignment
Activating a message trace
Firmware update of TIM modules
Downloading a new parameter assignment to the TIM modules
Note
Diagnostics functions that are also available in the SIMATIC Manager are described here
with the emphasis on diagnostics of TIM modules.
3.1.1 Starting the program and types of access
Opening the Diagnostics and Service tool
The SINAUT Diagnostics and Service tool is opened in the Windows start menu
SIMATIC /
SINAUT ST7 / Diagnostics and Service
.
You can access the module-specific diagnostic information alternatively over:
Accessible nodes
the
SINAUT subscriber list
of the STEP 7 project
NOTICE
Regardless of whether you access this information using
Accessible nodes
or the
SINAUT subscriber list
, unless you activate the PG routing function, you can only
access subscribers of the subnet of the local MPI bus to which the PG is connected.