Technical data
SINAUT TD7 software package for the CPU
2.7 Test blocks
Software
324 System Manual, 07/2009, C79000-G8976-C222-07
2.7.2 DB TestCopyData
Structure of DB TestCopyData
The following table shows the structure of the DB TestCopyData:
Address Name Format Explanation
DBB 0 OperationMode BYTE Mode
DBB 1 Recv_TgrmType BYTE Receive filter: Message type (MT)
DBW 2 Recv_DestSubscr INT Receive filter: Destination
subscriber no.
DBW 4 Recv_DestObject INT Receive filter: Destination object
no.
DBW 6 Recv_SourceSubscriber INT Receive filter: Source subscriber
no.
DBW 8 Recv_SourceObject INT Receive filter: Source object no.
DBW 10 Recv_StartIndex INT Receive filter: Start index no.
DBW 12 Recv_TgramCounter INT Number of copied received
messages
DBB 14 SpareDBB14 BYTE Reserve
DBB 15 Send_TgrmType BYTE Send filter: Message type (MT)
DBW 16 Send_DestSubscr INT Send filter: Destination subscriber
no.
DBW 18 Send_DestObject INT Send filter: Destination object no.
DBW 20 Send_SourceSubscriber INT Send filter: Source subscriber no.
DBW 22 Send_SourceObject INT Send filter: Source object no.
DBW 24 Send_StartIndex INT Send filter: Start index no.
DBW 26 Send_TgramCounter INT Number of copied sent messages
DBB 28 RetVal BYTE Error information:
0 = No error
1 = DB TestCopyData too short
10 = Unknown operating mode
DBB 29 SpareDBB29 BYTE Reserve
DBB 30 SpareDBB30 BYTE Reserve
DBB 31 TestCopyStatus BYTE Status byte for Testcopy
operation
DBB 32 TestCopyCmdByte BYTE Command byte for Testcopy
operation
DBB 33 TestCopyDelCount BYTE Loop counter for TestCopy delete
function
DBW 34 NextFreeCopyByte INT Address of the next free
TestCopyBuffer byte
DBD 36 StartTimeSFC64 DINT SFC64 time at the start of the
copy procedure
DBB 40 TestCopyBuffer[0] BYTE Copy area, byte 0
DBB 41 TestCopyBuffer[1] BYTE Copy area, byte 1