Technical data
Configuration software for SINAUT ST7   
1.5 Setting TIM module parameters 
  Software 
32  System Manual, 07/2009, C79000-G8976-C222-07 
Example of time synchronization 
It is assumed that all SINAUT nodes in the network need to be synchronized. 
Figure 1-12  Example of time synchronization: Network section 1 - MPI / classic WAN 
●  ST7cc 
No settings are necessary here. 
●  Master TIM 4R / master TIM 4RD 
Time synchronization on the MPI bus must be enabled for both TIMs. An interval of 1 
minute is recommended. 
Note 
ST7cc and ST7sc expect time synchronization on the MPI bus at intervals of 1 minute or 
less. Longer intervals cause error messages. 
In this example, the "master TIM 4RD" takes over the master function after startup 
because it has a DCF77 receiver. Once this TIM has received a valid time of day, the 
ST7cc PC and the "master TIM 4R" are synchronized over MPI. If the TIM with a DCF77 
receiver fails, the "master TIM 4R" can take over the master function. 