Technical data
SINAUT TD7 software package for the CPU
2.6 Blocks for optional expansion
Software
318 System Manual, 07/2009, C79000-G8976-C222-07
Table 2- 7 Structure of an SMS object in DB SMS_Data
Number of data words Short name Meaning
Max. 62 SMS text SMS text string, max. 122 characters long
1 Year Month
1 Day Hours
1 Minute Second
Acquisition time stamp for the most recently sent
incoming SMS
1 Year Month
1 Day Hours
1 Minute Second
Acquisition time stamp for the most recently sent
outgoing SMS
1 CurrentMessageStatus Typical-internal SMS processing status (see
description of CurrentMessageStatus)
1 Status incoming
SMS
Status outgoing
SMS
Most recent SMS status received by the CPU from
the TIM or SMS-C (see description of the Status
incoming SMS)
1 TIM ID for incoming SMS ID number for incoming SMS assigned by the TIM
1 TIM ID for outgoing SMS ID number for outgoing SMS assigned by the TIM
1 Year Month
1 Day Hours
1 Minute Second
Time stamp of the status message most recently
transferred by the TIM to the CPU
1 LastControlMessage Most recent control instruction from the CPU to the
TIM (without time stamp)
1 RemainingValidPeriodP Time remaining in validity period of the incoming
SMS
1 RemainingValidPeriodN Time remaining in validity period of the outgoing
SMS
1 SupervisionTime Time remaining in the supervision time until
incoming or outgoing SMS must be transfer to the
SMS-C at the latest
1 PreviousMessageAddress Previous address (for chained job list)
1 NextMessageAddress Next address (for chained job list)
1 MessageNumber Message number of the SMS for identification and
diagnostics
CurrentMessageStatus
The meaning of the status bits in CurrentMessageStatus:
Bit no.
Status .15 .14 .13 .12 .11 .10 .9 .8 .7 .6 .5 .4 .3 .2 .1 .0
Bit .1 .0 Status of the SMS after incoming signal edge:
0 0 0 = Job complete without error
0 1 1 = TIM confirms: (incoming) SMS received
1 0 2 = SMS-C confirms: (incoming) SMS received
1 1 3 = Job ended with error