Technical data

SINAUT TD7 software package for the CPU
2.6 Blocks for optional expansion
Software
316 System Manual, 07/2009, C79000-G8976-C222-07
No SMS messages can be accepted for processing when:
DB-specific delete job active
A DB specific status request is in progress e.g. when the CPU is being
restarted
The instance DB or DB SMS_Data is being initialized
There must be a reaction to changes at the Enable input
A switchover between the main and backup mobile phone is in progress
or, in general, the change of a mobile telephone number including a new
SMS transfer.
Access to the SMS-C or the SMS-C itself is disrupted
The keyword in DB SMS_Data cannot be found
The typical is then temporarily blocked and sets bit .9.
Name: ReloadMobilPhoneNo
Declaration: IN_OUT
Data type BOOL
Explanation If the telephone number or one or both mobile phones needs to be changed
online, activation of the new telephone numbers can be triggered over this
input.
TRUE or FALSE
No parameter specified: Default value FALSE is valid
Range of
values:
Input
Bit memory
Data bit
I 0.0 ... I n.7
M 0.0 ... M n.7
DBm.DBX 0.0 ... n.7
After the user has changed the mobile phone numbers in DB SMS_Data,
the input can be set and the new telephone number data activated online.
Otherwise the typical always uses the telephone numbers stored in DB
SMS_Data when the typical detects a signal change from FALSE to TRUE at
the ENABLE input.
If you do not require the parameter, simply leave it open.
Note
This is an in/out parameter (declaration IN_OUT). It is difficult to specify local bit memory
with this parameter type and this should not be used.