Technical data
SINAUT TD7 software package for the CPU
2.6 Blocks for optional expansion
Software
System Manual, 07/2009, C79000-G8976-C222-07
303
Data type BOOL
Explanation Group message: A command output error has been detected in a station.
Range of
values:
Output
Bit memory
Data bit
Q 0.0 ... I n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
If the parameter is not required, specify a memory bit or data bit that can be
used as a scratchpad memory.
For more detailed information on this parameter, refer to the section
Function.
2.6.6 FC PartnerStatus
Function
The FC PartnerStatus can show the current status ’disrupted’ or ’OK’ for a maximum of 8
SINAUT subscribers.
The FC can be called at any point in the cyclic SINAUT program (in OB1).
If you want to monitor the status of more than 8 subscribers, an appropriate number of
PartnerStatus FCs must be included in the SINAUT program.
A SINAUT subscriber (partner) can be an ST7 CPU or an ST7cc to which a connection was
configured, or a local TIM.
One bit per subscriber is reserved in the PartnerStatus output byte to indicate the status of
the respective subscriber:
FALSE (or 0): Subscriber is disrupted (or the corresponding input parameter is not being
used, i.e. configured as 0, or subscriber is unknown).
TRUE (or 1): Subscriber OK
Explanation of the parameters
Name: Partner1 ... Partner8
Declaration: INPUT
Data type INT
Explanation SINAUT subscriber number of the subscriber to be monitored
Range of
values:
0 or 1 ... 32000
0 = Dummy value for unrequired parameter
1 ... 32000 = Number of the subscriber to be monitored