Technical data

SINAUT TD7 software package for the CPU
2.6 Blocks for optional expansion
Software
System Manual, 07/2009, C79000-G8976-C222-07
295
Data type BOOL
Explanation An interval is set for the FC.
Range of values: TRUE or FALSE
FALSE = no, in other words, a time is set.
TRUE = Yes, in other words, an interval is set.
You will find examples of setting a point in time or a time interval following
the description of the parameters.
Name: Hour_Minute
Declaration: INPUT
Data type WORD
Explanation Specifies the values for hours and minutes.
Further explanation: Refer to Month_Year parameter below.
Name: Second_Day
Declaration: INPUT
Data type WORD
Explanation Specifies the values for seconds and day.
Further explanation: Refer to Month_Year parameter below.
Name: Month_Year
Declaration: INPUT
Data type WORD
Explanation Specifies the values for month and year.
Range of values: 00 ... 99, or FF
Each parameter has two parts, each of the two values per parameter is
specified with two digits as a BCD coded value. The first two digits contain
the values for hours, seconds or month; the two remaining digits specify the
minutes, day or year. Enter FF for parameters you do not require.
The parameters allowed depend on the particular parameter and the
IntervalMode parameter. For more information, refer to examples following
the descriptions of these parameters.
Name: TriggerOutput
Declaration: OUTPUT
Data type BOOL
Explanation Trigger output.