Technical data

SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
System Manual, 07/2009, C79000-G8976-C222-07
275
Range of
values:
Bit memory
Data bit
No parameter specified:
Default value FALSE is valid.
M 0.0 ... M n.7
DBm.DBX 0.0 ... n.7
You can use this input parameter when the parameter is entered by
software, for example at an operator panel (OP). The RetransmitAll input
should then be set using a function key on the OP. When a 1 signal is
detected at the RetransmitAll input, the entire data area defined by
ParameterInput is transmitted. Changes are not checked.
The RetransmitAll input is reset automatically. You should therefore only
specify memory or data inputs as the input. The automatic reset would not
work with a digital input. Since there is no change check, this would lead to
continuous transmission of all parameter values as long as the digital input
has a 1 signal.
The RetransmitAll input can also be used as an option in addition to Release
or ContinuousEnterFunct = TRUE when new parameter values were entered
but could not be transmitted to the partner (for example because of a
disrupted connection or because the partner object was previously set to
’local’). You can then trigger transmission of the entire data area defined by
ParameterInput using the RetransmitAll input. All changes that were
previously entered but are not yet available at the partner are consistently
included.
The RetransmitAll input can also be used as an independent transmission
trigger when you always want to send all entries and not just those that have
changed. You should then use RetransmitAll instead of Release that only
sends the changed parameter values.
Data checks:
The same safety checks are carried out as with ContinuousEnterFunct =
TRUE. Refer to the description there.
If you do not require the parameter, simply leave it open.
Note
This is an in/out parameter (declaration IN_OUT). It is difficult to specify local bit memory
with this parameter type and this should not be used.
Name: ApplyRemoteParamMan
Declaration: IN_OUT
Data type BOOL
Default: FALSE
Explanation Trigger input for synchronization of the input area with the returned area.