Technical data

SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
System Manual, 07/2009, C79000-G8976-C222-07
273
Range of
values:
Output
Bit memory
Data bit
No parameter specified:
Default value FALSE is valid.
Q 0.0 ... Q n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
A parameter can also be set locally at the partner object that receives the
parameter. The partner object then must be set to ’local’ at the Local input
parameter (see FB Par12D_R below). The current status of the Local input
parameter is reported by the partner object and displayed here at the
LocalOperation output. As long as the partner object is set to 'local', no
parameters are accepted there from other locations.
After startup of the local or partner PLC, or after restoring a connection, an
automatic general request ensures that the current, local, valid status is
displayed at LocalOperation.
How to read out the time stamp received with the data is described in the
section Notes on the SINAUT time stamp.
If you do not require the parameter, simply leave it open.
Name: NewData
Refer to
Parameters you require often (Page 223).
Explanation
of the
typical-
specific
outputs
Whenever the FB has received new data and has output it to the outputs
ReturnedParameter or LocalOperation, the NewData output is set to TRUE
for one OB1 cycle.
Name: Release
Declaration: IN_OUT
Data type BOOL
Default: FALSE
Explanation Trigger input for sending the currently pending parameter values