Technical data
SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
270 System Manual, 07/2009, C79000-G8976-C222-07
Note
The changed data area that is transmitted consists of the first and the last double word in
which a change was detected and all words located in between, even if these have not
changed.
Example:
The area to be read is 10 double words long. In this case, changes were detected in the 2nd,
5th and 8th double words. The transmitted area is therefore from the 2nd to the 8th double
word inclusive.
Name: ApplyRemoteParamAuto
Declaration: IN
Data type BOOL
Default: FALSE
Explanation Automatic synchronization of the input area with the returned area.
Range of
values:
TRUE or FALSE
No parameter specified: Default value FALSE is valid.
If ApplyRemoteParamAuto = TRUE, the input area ParameterInput is
automatically synchronized with the ReturnedParameter area. All the
parameter values from the ReturnedParameter area are then copied to the
ParameterInput area. The send buffer is also synchronized with the returned
parameter values. Automatic synchronization is then always performed
when new data is received from the partner object (Par12D_R).
If you do not require the parameter, simply leave it open. The default value
FALSE then applies; in other words no automatic synchronization is
performed.
Name: ParameterInput
Declaration: INPUT
Data type ANY
Default: P#P 0.0 VOID 0 (null pointer)
Explanation Parameter input area.