Technical data
SINAUT TD7 software package for the CPU   
2.5 Data point typicals 
  Software 
268  System Manual, 07/2009, C79000-G8976-C222-07 
Explanation of the parameters 
Names:  PartnerNo 
  PartnerObjectNo 
  Enabled 
Refer to 
Parameters you require often (Page 223). 
Name:  EnterInput 
Declaration:  INPUT 
Data type  BOOL 
Default:  FALSE 
Explanation  Enter input. 
TRUE or FALSE 
No parameter specified: Default value FALSE is valid 
  Range of 
values: 
Input 
Bit memory 
Data bit 
I 0.0 ... I n.7 
M 0.0 ... M n.7 
L 0.0 ... L n.7 
DBm.DBX 0.0 ... n.7 
  The transmission of the parameter value at ParameterInput can be triggered 
over this input by a signal edge change. 
A signal change at EnterInput is only taken into account when the parameter 
ContinuousEnterFunct = FALSE. If this condition is fulfilled, a transition from 
0 to 1 causes the parameter values specified at ParameterInput to be 
entered and transmitted. Changes are not checked. The entire data area 
specified by ParameterInput is always transmitted. 
This method of transmission triggering is suitable for input with appropriate 
hardware, for example at a console or control panel. For more detailed 
information and related parameters, refer to the section Function. 
If you do not require the parameter, simply leave it open. 
Data checks: 
•  The parameters that are read in are then transmitted if no error is 
detected during the 1-out-of-n check, and if the central enable memory bit 
is set. This is automatically set by FC Safe following a selected time 
delay set there (see FC Safe, InputDelayTime parameter). The input area 
is then only read in by the FB when a 0 signal was detected at EnterInput 
for at least one OB1 cycle. 
•  When a 1-out-of-n error is detected at the "hardware" input, the entered 
parameters are no longer processed. New parameters are read in again 
only when no "hardware" input has been acquired in the PLC for one 
OB1 cycle; in other words, not only for this block but also for all other 
command, setpoint and parameter blocks with "hardware" input. The FB 
enters the detected 1-out-of-n error in the diagnostic buffer (event ID 
B172). The error status is also indicated over the InputError output of FC 
Safe (see FC Safe, InputError parameter) and continues to be indicated 
as long as the error remains. 










