Technical data

SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
System Manual, 07/2009, C79000-G8976-C222-07
261
Data type WORD
Default: 0 (W#16#0)
Explanation Output word for a returned setpoint.
Range of
values:
Output words
Memory words
Data words
QW0 ... QWn
PQW0 ... PQWn
MW0 ... MWn
LW0 ... LWn
DBm.DBW0 ... n
The partner object receiving the setpoint reports back the currently valid
local setpoint. This value is displayed at the ReturnedSetpoint output. If the
partner object is set to ’local’ and if an input is made there, then the setpoint
changed locally is displayed here at ReturnedSetpoint.
After startup of the local or partner PLC, or after restoring a connection, an
automatic general request ensures that the current, local, valid setpoint is
displayed at ReturnedSetpoint.
How to read out the time stamp received with the data is described in the
section Notes on the SINAUT time stamp.
If you do not require the parameter, simply leave it open.
Name: LocalOperation
Declaration: OUTPUT
Data type BOOL
Default: FALSE
Explanation Return message from the partner object: Object is set to local operation.
Range of
values:
Output
Bit memory
Data bit
No parameter specified:
Default value FALSE is valid.
Q 0.0 ... Q n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
A setpoint can also be set locally at the partner object that receives the
setpoint. The partner object then must be set to ’local’ at the Local input
parameter (see FB Set01W_R below). The current status of the Local input
parameter is reported by the partner object and displayed here at the
LocalOperation output.
After startup of the local or partner PLC, or after restoring a connection, an
automatic general request ensures that the current, local, valid status is
displayed at LocalOperation.
How to read out the time stamp received with the data is described in the
section Notes on the SINAUT time stamp.
If you do not require the parameter, simply leave it open.