Technical data
SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
258 System Manual, 07/2009, C79000-G8976-C222-07
Note
Since the parameter is an IN_OUT parameter, direct I/O output of the command byte to
PQB0 ... PQBn is not permitted. It is also difficult to specify local bit memory with this
parameter type and this should not be used.
2.5.10 ST7 setpoint typical FB Set01W_S
Function
Send 1 setpoint (16 bits) and receive current local setpoint.
Note
With FB Set01W_S, data can only be transmitted when FC Safe is included at the end of the
cyclic SINAUT program.
Explanation of the parameters
Names: PartnerNo
PartnerObjectNo
Enabled
Refer to
Parameters you require often (Page 223).
Name: EnterInput
Declaration: INPUT
Data type BOOL
Default: FALSE
Explanation Enter input (for 'hardware' setpoint).