Technical data
  SINAUT TD7 software package for the CPU 
  2.5 Data point typicals 
Software 
System Manual, 07/2009, C79000-G8976-C222-07 
253 
2.5.8  ST7 command typical FB Cmd01B_S 
Function 
Send 1 byte commands (1-out-of-8 ST1 format). 
Note 
With FB Cmd01B_S, data can only be transmitted when FC Safe is included at the end of 
the cyclic SINAUT program. See also 'The cyclic OB1 program for a master station' in 
section 
Cyclic SINAUT program in OB1 (Page 206). 
Explanation of the parameters 
Names:  PartnerNo 
  PartnerObjectNo 
Refer to 
Parameters you require often (Page 223). 
Name:  Enabled 
Declaration, data type , default and range of values: Refer to 
Parameters you require often 
(Page 
223). 
Explanation  Whether or not processing of the block is enabled must be specified. 
If processing is enabled, all the functions of the FB execute. 
If processing is disabled the FB only checks to see if the disabled status has 
been canceled. The FB cannot communicate on the organizational level in 
this status because FB Cmd01B_S cannot send or receive organizational 
messages. 
Name:  CommandInputByte_HW 
Declaration:  INPUT 
Data type  BYTE 
Default:  0 (B#16#0) 
Explanation  Command input byte for hardware input. 










