Technical data
SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
246 System Manual, 07/2009, C79000-G8976-C222-07
Name: AnalogOutput_1 … _4
Declaration: OUTPUT
Data type WORD
Default: TRUE
Explanation 0 (W#16#0)
Range of
values:
I/O words
Memory words
Data words
PQW0 ... PQWn
MW0 ... MWn
LW0 ... LWn
DBm.DBW0 ... n
You can select where the individual analog values received by the FB are
output. I/O words from analog output modules, data words from a data block
and memory words can be mixed as required.
How to read out the time stamp received with the data is described in the
section Notes on the SINAUT time stamp.
If you do not require parameters, simply leave them open.
Name: NewData
Refer to
Parameters you require often (Page 223).
Explanation
of the
typical-
specific
outputs
Whenever the FB has received new data and has output it to the outputs
AnalogOutput_1 through AnalogOutput_4, the NewData output is set to
TRUE for one OB1 cycle.
2.5.6 ST7 counted value typicals FB Cnt01D_S and FB Cnt04D_S
Function
[Cnt01D_S] send 1 counted value (32-bit ST1 format).
[Cnt04D_S] send 4 counted values (32-bit ST1 format).
Explanation of the parameters
Names: PartnerNo
PartnerObjectNo
Enabled
ImageMemory
Conditional
Unconditional
Permanent