Technical data
  SINAUT TD7 software package for the CPU 
  2.5 Data point typicals 
Software 
System Manual, 07/2009, C79000-G8976-C222-07 
245 
  Range of 
values: 
0 ... 32767 [s] 
No parameter specified: Default value 0 s is valid. 
  Transmission of an analog value located in the overflow or underflow range 
(7FFFH or 8000H) is suppressed for the time period specified here. The 
value 7FFFH or 8000H is only sent after this time has elapsed, if it is still 
pending. If the value returns to below 7FFFH or above 8000H again before 
this time elapses, it is immediately sent again as normal. The suppression 
time is started again for the full duration the next time 7FFFH or 8000H is 
acquired. 
This is typically used for temporary suppression of current values that may 
occur when powerful pumps and motors are started. The analog input may 
exceed several times the maximum range under some circumstances. 
Suppression prevents these values from being signaled as faults in the 
control center system. 
The suppression is adjusted to analog values that are acquired by the S7 
analog input modules as raw values. These modules return the specified 
values for the overflow or underflow range for all input ranges (also for life-
zero inputs). When the user provides specific values, fault suppression is 
only possible if these also adopt the values 7FFFH or 8000H when the 
permitted ranges are exceeded. If this is not the case, the parameter does 
not need to have a value entered. 
The parameter can also be used in combination with the mean value 
calculation temporary suppression of the values 7FFFH or 8000H (see 
description of the MeanValueGeneration) parameter. 
When no parameter is specified, the default value of 0 seconds applies. An 
acquired value of 7FFFH or 8000H is then sent immediately when it is first 
detected or, with mean value calculation, as an invalid mean value for the 
current mean value calculation period. 
2.5.5  ST7 analog value typical FB Ana04W_R 
Function 
Receive 4 analog values (16-bit value in the INT format). 
Explanation of the parameters 
Names:  PartnerNo 
  PartnerObjectNo 
  Enabled 
Refer to 
Parameters you require often (Page 223). 