Technical data

SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
236 System Manual, 07/2009, C79000-G8976-C222-07
Range of
values:
Output byte
Memory bytes
Data bytes
QB0 ... QBn
PQB0 ... PQBn
MB0 ... MBn
LB0 ... LBn
DBm.DBB0 ... n
Where the binary information such as status messages, alarms etc is to be
output can be selected byte by byte. Output bytes in the process output
image, I/O bytes directly on digital output modules, data bytes of a data
block and memory bytes can be mixed as required.
How to read out the time stamp received with the data is described in the
section Notes on the SINAUT time stamp.
If you do not require parameters, simply leave them open.
Name: NewData
Refer to
Parameters you require often (Page 223).
Explanation
of the
typical-
specific
outputs
Whenever the FB has received new data and has output it to the output
bytes OutputByte_1 through OutputByte_4, the NewData output is set to
TRUE for one OB1 cycle.
2.5.4 ST7 analog value typical FB Ana04W_S
Function
Send 4 analog values (16-bit value in the INT format).
FB Ana04W_S transfers the 4 analog values:
As instantaneous values
At the time of the transmission, the currently pending analog value is acquired and
transferred to the partner.
or
As mean values
The pending analog value is accumulated at selectable intervals. At the time of the
transmission, a mean value is formed from the total value and transferred to the partner.
Note
The processing parameters such as threshold, smoothing factor etc. exist only once in a
typical. These parameters apply to all 4 analog values in common; in other words, it is not
possible to set the parameters for the individual analog values. For this reason, each
typical should only acquire analog values that can be processed in the same way.