Technical data
SINAUT TD7 software package for the CPU
2.5 Data point typicals
Software
228 System Manual, 07/2009, C79000-G8976-C222-07
• Sending process typicals
(Cmd01B_S, Set01W_S, Par12D_S)
The parameter setting PartnerObjectNo = 0 is not permitted!
If the parameter setting is incorrect (< 1 or > 32000), an error message to
this effect is entered in the diagnostic buffer (event ID B102). The CPU
does not change to STOP. The FB is then no longer processed, however,
until the parameter assignment error has been corrected.
• Receiving process typicals
(Bin04B_R, Ana04W_R, Cnt01D_R/Cnt04D_R, Dat12D_R)
The parameter setting PartnerObjectNo = 0 is not permitted!
If the parameter setting is incorrect (< 1 or > 32000), an error message to
this effect is entered in the diagnostic buffer (event ID B102). The CPU
does not change to STOP. The FB is then no longer processed, however,
until the parameter assignment error has been corrected.
If the PLC receives a message for the object set here, the system checks
whether the source object number in the message is identical to the
PartnerObjectNo set here. If they are different, the received information is
discarded. An error message to this effect is entered in the diagnostic
buffer (event ID B131).
Enabled
Name: Enabled
Declaration: INPUT
Data type BOOL
Default: TRUE
Explanation Enable block processing
TRUE or FALSE
No parameter specified: Default TRUE is valid
Range of
values:
Input
Bit
memory
Data bit
I 0.0 ... I n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
Whether or not processing of the block is enabled must be specified.
If processing is enabled, all the functions of the FB execute.
The response is different if processing has not been enabled: