Technical data

SINAUT TD7 software package for the CPU
2.1 Overview
Software
System Manual, 07/2009, C79000-G8976-C222-07
191
Step 1
Copy the UDTs that you want to change in your program from the symbol table of the
TD7 library to the symbol table of the first CPU.
Change the numbers of the SINAUT UDTs to the numbers you require in the symbol
table.
Save the symbol table.
Then copy the rows with the changed UDT numbers to the symbol tables of all other
CPUs of your project. Do not forget to save all the modified symbol tables.
Step 2
Once all the symbol tables have the required values and have been saved, change to the
'Subscriber Administration' SINAUT ST7 Configuration Tool.
Click the 'Save' button. An extra dialog 'Properties' opens (see following figure).
Make sure that a check mark is entered in front of the following options in this dialog:
'System data blocks for TIMS and CPUs'
and
'SINAUT TD7 blocks for CPUs'
and a dot in front of 'for all CPUs'. Then click on 'OK'.
Figure 2-12 Dialog for triggering compilation of the SINAUT TD7 blocks
After you have saved, all the SINAUT blocks basically required are entered in the block
directories of all CPUs, and possibly also the UDTs with the new numbers you have