Technical data
SINAUT TD7 software package for the CPU   
2.1 Overview 
  Software 
190  System Manual, 07/2009, C79000-G8976-C222-07 
belong to the auxiliary block category), the numbers of these blocks can be changed directly 
in the block directory. Do not forget, however, to make the same number change in the 
symbol table of the CPU. 
Note 
Never use this method to change the numbers of the SINAUT data blocks. These are the 
data blocks with the symbolic names 
BasicData
, 
XComData01
, 
XComData02
 etc., 
PComData01
, 
PComData02
 etc. and 
BComData01
, 
BComData02
 etc. 
If you want to make the same changes for more than one CPU, the most efficient method is 
to make the changes first in the block directory and the symbol table of one CPU. You can 
then copy the modified blocks from the block directory of the finished CPU to the other CPUs 
and then do the same for the symbol tables. 
Changing the numbers of UDTs 
The prerequisite for using the instructions here is as follows: 
●  You only want to change the numbers of SINAUT UDTs. 
Initial situation 
You have completed the configuration of your SINAUT installation including the connection 
configuration with the appropriate SINAUT configuration tool. You have not yet saved in the 
'Subscriber Administration' SINAUT tool. The result is that there are not yet any SINAUT 
blocks in the program directories of the CPUs. The block directory CPU contents, for 
example, only the system data and OB1 as shown in the following figure. 
Figure 2-11  Example of a project (still without user or SINAUT program) 
Making the change 
The change to the UDT numbers is made indirectly using the symbol table of the CPU with 
the aid of the 'Subscriber Administration' SINAUT Configuration Tool. 










