Technical data

SINAUT TD7 software package for the CPU
2.1 Overview
Software
System Manual, 07/2009, C79000-G8976-C222-07
189
Figure 2-9 Renaming blocks in the dialog
If the block number is changed using this dialog, the number change is automatically
included in the symbol table. This can be recognized because the renamed block in the
block directory is displayed immediately with the corresponding name from the TD7 library.
Figure 2-10 Renaming with automatic symbol assignment
If you copy several blocks at one time, the dialog is displayed for each block whose number
is already being used. You can therefore copy all the required blocks per CPU at one time
and then adapt the block numbers and entries in the symbol table as necessary.
If the dialog does not appear when you copy blocks, there is no conflict with existing blocks.
If you nevertheless want to give blocks a different number, you must change these numbers
directly in the block directory and also adapt the relevant entries in the symbol table
(although the symbolic name of a SINAUT block was entered automatically in the symbol
table of the destination CPU when the blocks were copied from the TD7 library, the new
numbers are not taken into account since they were not changed initially during copying).
If you want to change one of the blocks already stored by the SINAUT tool (here, this can
only involve the blocks FC122 Startup and FC127 BasicTask because all other blocks