185
Block no. Symbolic name Aux.
block
Required (SINAUT) auxiliary
blocks
Explanation
FB110 Cmd01B_S - DB127 BasicData,
FC123 Create, FC126 Search
ST7 command object, send 1 byte
commands (1-out-of-8 ST1 format).
FB111 Cmd01B_R - DB127 BasicData,
FC126 Search
ST7 command object, receive 1 byte
commands (1-out-of-8 ST1 format).
FB116 Set01W_S - DB127 BasicData,
FC123 Create, FC126 Search
ST7 setpoint object, send 1 setpoint
(16 bits) and receive current local
setpoint.
FB118 Par12D_S - DB127 BasicData,
FC123 Create, FC126 Search
ST7 parameter object, send max. 12
double words with parameters and
receive current local parameters.
FB119 Par12D_R - DB127 BasicData,
FC123 Create, FC126 Search
ST7 parameter object, receive max. 12
double words with parameters and
send current local parameters.
FB124 SMS_Control - DB127 BasicData,
FC123 Create,
FC125 Diagnose, FC126 Search
Block for sending SMS messages.
FB125 PCom Yes DB127 BasicData,
FC124 Distribute,
FC125 Diagnose, FC126 Search
Block for communication over a
peripheral bus connection (SFCs
WR_REC and RD_REC are used).
FB126 XCom Yes DB127 BasicData,
FC124 Distribute,
FC125 Diagnose, FC126 Search
Communication block for an
unconfigured X connection (SFCs
X_SEND and X_RCV are used).
FB127 BCom Yes DB127 BasicData,
FC124 Distribute,
FC125 Diagnose, FC126 Search
Communication block for a configured
communication block connection
(SFBs BSEND and BRCV are used).
Functions FC
FC113 PartnerMonitor - DB127 BasicData,
FC125 Diagnose, FC126 Search
Allows the display of important status
information and control for a SINAUT
subscriber.
FC114 Trigger - DB127 BasicData,
FC125 Diagnose
Sets an output at a defined time or at a
defined interval.
FC115 PartnerStatus - DB127 BasicData,
FC125 Diagnose, FC126 Search
Displays the connection status for up
to 8 SINAUT subscribers.
FC116 Safe - DB127 BasicData Block for saving command and
setpoint input.
FC117 PulseCounter - DB127 BasicData Block for acquiring up to 8 counter
inputs
FC118 TestCopy - DB127 BasicData Test block for logging received and/or
sent messages.
FC119 ListGenerator300 - DB127 BasicData Block for generating an object list.
Version for S7-300.
FC120 ListGenerator400 - DB127 BasicData Block for generating an object list.
Version for S7-400.
FC121 TimeTask - DB127 BasicData,
FC125 Diagnose
Block for keeping the date and time on
a CPU
FC122 Startup - DB127 BasicData Startup block.
FC123 Create Yes DB127 BasicData,
FC125 Diagnose, FC126 Search
Block for creating messages and
entering them in the send buffer.